- 96 -
000414AG
8 - Maintenance
Resetting the time remaining to change the grid standard
From the time a valid grid standard is entered and the inverter is turned
on, a period of 24 hours is available to modify the grid standard setting.
The 24 hours are counted only when the inverter is turned on.
Check that the date and time are set correctly. Otherwise it may not be possible to access the
“Nation Select” menu to reset the timer.
After this period the “Nation Select.” functionality will be blocked, and any
subsequent changes can only be made using a password provided on
request by ABB.
To request this password, contact the ABB Customer Service and com-
municate the serial number (S/N) of the inverter and the “Authorization
Key” code, which can be obtained by selecting the sub-menu SETTINGS
> NATION > NATION SELECT
Settings
ENTER
Password 0000
ENTER
Nation
ENTER
Nation Select
ENTER
Auth. Key
123456
After obtaining the password, select SETTINGS > NATION > NATION
SELECT, press ENTER and digit the password supplied by ABB
Settings
ENTER
Password 0000
ENTER
Nation
ENTER
Nation Select
ENTER
Auth. Key
123456
ENTER
Password
0*****
After you have entered the password, the “Nation” value can be changed
for a further period of 24 hours.