7 - Operation
The table below shows the parameters that can be changed and the
range of values that may be set for each:
Parameter Description Setting range
Amorphous
Mode
Enables Amorphous Mode in the event that the negative input pole is
grounded by installing the Negative Grounding Kit (not available)
Enabled/Disabled
Set U>> Grid over-voltage (OV) threshold (extended range) Unom … Unom x 1.3
Set U<< Grid under-voltage (UV) threshold (extended range) 10V … Unom
Set U> Grid over-voltage (OV) threshold (restricted range) Unom … Unom x 1.3
Set U> (10Min) Grid over-voltage (OV) threshold (average grid voltage value) Unom … Unom x 1.3
Set U< Grid under-voltage (UV) threshold (restricted range) 10V … Unom
Set F>> Grid over-frequency (OF) threshold (extended range) Fnom … Fnom + 5Hz
Set F<< Grid under-frequency (UF) threshold (extended range) Fnom - 5Hz … Fnom
Set F> Grid over-frequency (OF) threshold (restricted range) Fnom … Fnom + 5Hz
Set F< Grid under-frequency (UF) threshold (restricted range) Fnom - 5Hz … Fnom
Set Uconn> Max. permissible voltage during checks prior to grid connection Unom … Unom x 1.3
Set Uconn< Min. permissible voltage during checks prior to grid connection 10V … Unom
Set Fconn> Max. permissible frequency during checks prior to grid connection Fnom … Fnom + 5Hz
Set Fconn< Min. permissible frequency during checks prior to grid connection Fnom - 5Hz … Fnom
Set Time U>> Over-voltage U>> protection tripping time
0 … 327670mS
Set Time U<< Under-voltage U<< protection tripping time
Set Time U> Over-voltage U> protection tripping time
Set Time U< Under-voltage U< protection tripping time
Set Time F>> Over-frequency F>> protection tripping time
Set Time F<< Under-frequency F<< protection tripping time
Set Time F> Over-frequency F> protection tripping time
Set Time F< Under-frequency F< protection tripping time
Set time conn 1 Grid check time prior to connection
0 … 65535mS
Set time conn 2 Grid check time prior to connection after a grid fault
Disable U>> Disables the U>> protection threshold
Enabled/Disabled
Disable U<< Disables the U<< protection threshold
Disable U> Disables the U> protection threshold
Disable U> (10m) Disables the U> (10Min) protection threshold
Disable U< Disables the U< protection threshold
Disable F>> Disables the F>> protection threshold
Disable F<< Disables the F<< protection threshold
Disable F> Disables the F> protection threshold
Disable F< Disables the F< protection threshold
Slow Ramp Enables gradual ramping up of power after the grid connection.
UAvg Derating Enables power derating mode due to high average grid voltage readings
OF Derating Selects the power derating mode in the event of grid over-frequency.
0 Derating disabled
1 BDEW derating
2 VDE-AR-N derating
3 CEI derating
4. New PW
This section of the menu allows you to change the settings menu pas-
sword (default 0000).
We advise you to memorize the new password with great care.
If the Password is lost you will not have access to the inverter, since there is no Reset function