5 - Installation
Connections to the communication and control board
Each cable which must be connected to the communication and control
board must pass through one of the two service cable glands.
• An M20 that takes cables from 7 mm to 13 mm in diameter. Gaskets
with two holes are supplied as standard to insert into the cable gland,
which enables two separate cables of a maximum cross-section of 5 mm
to be accommodated.
A B C
The procedure for opening the contacts of signal terminal block
13
and
tightening cables is as follows:
1) Insert the WAGO screwdriver (supplied) in slot with the screwdriver
facing downwards; insert the screwdriver until the clamp opens.
2) Insert the cable in the clamp.
3) Remove the WAGO screwdriver.
a b c
Each terminal accepts a cable with cross-section which can vary from
0.08 up to 2.5 mm².