2 - Characteristics
Characteristics and technical data
Table: Technical Data PVI-5000-TL-OUTD PVI-6000-TL-OUTD
Input
Absolute Maximum Input Voltage (Vmax,abs) 600 V
Rated Input Voltage (Vdcr) 360 V
Input start-up voltage (Vstart) 200 V (adj. 120...350 V)
Input operating interval (Vdcmin...Vdcmax) 0.7 x Vstart...
580
V
Input Nominal Power(Pdcr) 5150 Wp 6200 Wp
Number of Independent MPPT 2
Maximum input power for Each MPPT
(PMPPTmax)
4000 W
Input voltage interval (VMPPTmin ... VMPPTmax) to
Pacr (parallel MPPT conguration)
150…530 V 180...530 V
DC Power limiting for each MPPT
with Independent MPPT Conguration to Pacr,
maximum unbalance example
4000 W [220V≤VMPPT≤530V]
other channel:
Pdcr-4000W [90V≤VMPPT≤530V]
4000 W [220V≤VMPPT≤530V]
other channel:
Pdcr-4000W [120V≤VMPPT≤530V]
Maximum DC Input Current (Idcmax) / for each
MPPT (IMPPTmax)
36.0 A / 18.0 A
Maximum Return current (AC side vs DC side) Negligible
Number of DC Connection Pairs in Input for
each MPPT
2 pair 2 pair
DC Input Connector type (components indicated
or equivalents)
Connector PV Tool Free WM / MC4
Type of photovoltaic panels that can be con-
nected at input according to IEC 61730
Class A
Input protection
Reverse Polarity Protection Yes, from current limited source
Input Overvoltage protection for each MPPT -
Varistors
2
Maximum short-circuit current for each MPPT 22.0 A
Insulation Check Complying with the local standard
DC Disconnect Switch rating ( -S Version) Max. 25 A / 600 V
Output
AC Connection to the grid Monophase
Nominal AC output voltage (Vacr) 230 V
Output voltage range (Vacmin...Vacmin) 180...264 V
(1)
Nominal AC Output Power (Pacr @cosφ=1) 5000 W
(4)
6000 W
Maximum apparent Output power (Smax) 5560 VA 6670 VA
Maximum output current (Iacmax) 25.0 A 30.0 A
Contribution to short-circuit current 32.0 A 40.0 A
Inrush current Negligible
Maximum fault current <40 A rms (100ms)
Rated Output Frequency (fr) 50 Hz / 60 Hz
Output Frequency Range (fmin...fmax) 47...53 Hz / 57…63 Hz
(2)
Nominal Power Factor
> 0.995, adj. ± 0.9
with Pacr =5.0 kW
> 0.995, adj. ± 0.9
with Pacr =6.0 kW
Total Current Harmonic Distortion < 3.5%
AC Connections Type Terminal block (max cross-section 10 mm
2
); cable gland M32
Output protection
Anti-islanding Protection Complying with the local standard
Maximum AC Overcurrent protection 32.0 A 40.0 A
Output overvoltage protection - Varistors 2 (L - N / L - PE)