Start-up 103
Set parameter 98.08 AUTO LINE ID RUN to NO. This parameter setting prevents an
unnecessary ID run in case of
auxiliary power loss of the control
board.
Note: If the phase order changes,
set 99.07 LINE SIDE ID RUN to YES
to run the ID run once.
See the firmware manual.
SETTING UP FIELDBUS CONTROL (option +K454, +K458, +K466, or +K467)
Set the fieldbus parameters of the master control program
according to the external controller.
See PVS800 central inverters
firmware manual (3AUA0000058422
[English]) and the appropriate
fieldbus adapter module manual.
Check that the inverter can be seen from the PLC.
Check that you can read the signals from the inverter.
Check that you can start and stop the inverter.
Test control and actual values.
REGISTERING THE INVERTER
Fill a commissioning report for registering the inverter. You can
find the report on the InstalledBase web page
http://www180.abb.com:8010/logistics/InstalledBase/Pages/Insta
lledBase.aspx
If you do not have access to InstalledBase, submit a Membership
Request on the Installed Base main page. Note that
InstalledBase is only for ABB internal or ABB partner use.
Note: It is recommended to attach the parameter lists and back-
up files of the inverter and master control program to the report
as well.