Technical data 135
Terminal and lead-through data for the AC output power
cable
The AC busbars are tin-plated. Cable lugs suited to tin-plated materials can be used.
Inverter type No. of cable lead-throughs Ø60 mm (2.36”)
PVS800-57-0100kW-A 3
PVS800-57-0250kW-A 2 × 3
PVS800-57-0315kW-B 2 × 3
PVS800-57-0500kW-A 3 × 4
PVS800-57-0630kW-B 3 × 4
PVS800-57-0875kW-B 3 × 4
PVS800-57-1000kW-C 3 × 4
Inverter type
PVS800-57-
AC busbars PE busbar
Pcs Bolt size Tightening torque Screw Tightening torque
0100kW-A 3
M12
or ½”
70 N·m
(50 lb·ft)
M10
(3/8”)
30…44 N·m
2…32 lb·ft)
0250kW-A 3
0315kW-B 3
0500kW-A 3
0630kW-B 3
0875kW-B 6
1000kW-C 6
Terminals of PVS800-57-0250kW-A and -0315kW-B
Terminals of PVS800-57-0500kW-A,
-0630kW-B, - 0875kW-B and
-1000kW-C
Terminals of PVS800-57-0100kW-A