134 Technical data
The DC input power cable terminal data is given in the table below.
Units with fuse-protected DC input connections
DC busbars PE busbar
Inverter
type
PVS800-57-
Pcs (plus + minus)
Bolt
size
Tightening
torque
Bolt
size
Tightening
torque
+H382
+2H382
+4H382
+5H382
+8H382
+10H382
+12H382
+15H382
+16H382
+20H382
0100kW-A2---------
M12
or ½”
70 N·m
(50 lb·ft)
M10
or
3/8”
30…44 N·m
(2…32 lb·ft)
0250kW-A - 4 8 - 16 - - - - -
0315kW-B - 4 8 - 16 - - - - -
0500kW-A - - 8 10 16 20 24 30 - -
0630kW-B - - 8 10 16 20 24 30 - -
0875kW-B - - - - 162024303240
1000kW-C - - - - 162024303240
Units with MCB-protected DC input connections (option +H377)
Inverter
type
PVS800-57-
Photovoltaic switches PE busbar
Pcs
Max. wire size
(mm
2
)
6…50 (stranded cable)
6…70 (solid cable)
Tightening torque
3…4 N·m
(2.2…3.0 lb·ft)
Bolt
size
Tightening
torque
0100kW-A 4
M10
(3/8”)
30…44 N·m
(2…32 lb·ft)
Terminals of PVS800-57-0250kW-A, -0315kW-B,
-0500kW-A, -0630kW-B,- 0875kW-B and -1000kW-C
Terminals of PVS800-57-0100kW-A