Page #37 background imageLoading...
Page #37 background image
Mechanical installation 37
p
d
= 0.5 • v
m
2
= 0.5 • 1.1 • 5.5
2
= 17 Pa
The required pressure in the exit air duct is then, 1.5…2 • 17 Pa = 26…34 Pa, below the
pressure in the room.
For more information: Contact ABB.