EasyManua.ls Logo

ABB PVS800-57B

ABB PVS800-57B
84 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
36 Planning the electrical installation
Selecting the power cables
General rules
Dimension the DC input power and AC output power cables according to local
regulations:
Dimension the cable to carry the inverter load current. See chapter Technical data on
page 45 for the rated currents.
Select a cable rated for at least 90 °C (194 °F) maximum permissible temperature of
conductor in continuous use. Local regulations may require a higher temperature
rating.
The inductance and impedance of the PE conductor/cable (grounding wire) must be
rated according to permissible touch voltage appearing under fault conditions (so that
the fault point voltage will not rise excessively when a ground fault occurs).
Select an AC output cable rated for at least 0.6/1.0 kV AC and a DC input cable rated
for at least 1000 V DC.
A two-conductor system is allowed for the DC input cabling but a shielded cable can also
be used.
Symmetrical shielded cable is recommended for the AC output cabling; see section
Recommended AC output power cable types below. Compared to a four-conductor
system, the use of symmetrical shielded cable reduces electromagnetic emission of the
whole inverter system.
Note: When continuous metal conduit is employed, shielded cable is not required. The
conduit must have bonding at both ends as with cable shield.
To operate as a protective conductor, the shield conductivity requirements according to
IEC 61439-1 are shown below when the protective conductor is made of the same metal
as the phase conductors:
Cross-sectional area of
the phase conductors
Minimum cross-sectional
area of the corresponding
protective conductor
S (mm
2
) S
p
(mm
2
)
S <
16 S
16 < S <
35 16
35 < S S/2
Shield

Table of Contents

Other manuals for ABB PVS800-57B

Related product manuals