1MRK 500 124-UEN Section 3
HMI500
Operation Manual 33
Distributed busbar protection REB500
3.6 Configuration menu
Menu Item see section Description
Communication
Providing the communication option is selected, the protection
system can be connected with a station automation system (SAS)
or station monitoring system (SMS) via an interbay bus (IBB)
connection.
Device structure
Opens a new window that gives an overview of the configured
devices with its details.
Binary inputs/
outputs
Used to configure the binary inputs/outputs while engineering the
protection system. The data entered are normally provided in the
questionnaire filled in by the user. This dialog has three tabs:
Overview, Inputs, and Outputs.
Event text
configuration
Reference
source not
found.
In this
In this window all the event signals configured in the REB500 are
displayed. For each event signal a user specific text can be
configured (32 characters). The user can sort the list as per ABB
reference or the standard text.
LMI LED…
The local HMI of the REB500 IEDs has a certain number of LEDs.
Each of them can be assigned to an input or output signal.
Disturbance
recorder
Used to configure the disturbance recording of currents and
binary inputs and outputs in each bay and the central unit,
respectively. In addition, voltages can be recorded in the bay
units.