1MRK 500 124-UEN Section 3
HMI500
Operation Manual 69
Distributed busbar protection REB500
In the case of the optional IEC 61850-8-1 and IEC 60870-5-103 communication
protocols, the “Export” button creates files that can be used to configure the
communication interface at the remote end.
3.9.5 Settings
3.9.5.1 HMI500 settings
Some of the operator program functions can be customized:
Figure 55 HMI500 settings
3.9.5.2 Communication
Communication can be established with a REB500 system either via HMI front
connector or via the station bus.
Settings are provided for the TCP/IP address of the REB system to which
communication is being established.
It is possible to change between the communication modes On-line, Off-line and
Simulation. Selecting “On-line” causes HMI500 to check whether communication
with REB500 system can be established.
The checkbox “Enable security menu” and its influence to the sub-menus “Tools /
Security option” and “Tools / Security account management” is described under
“Security deployment guideline.
3.9.5.3 Parameters for reading and exporting event data
Settings are provided for the period for cyclically reading events and the separator
for an ASCII file when exporting events.