EasyManua.ls Logo

ABB rec670 - Page 55

ABB rec670
138 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table 26. Auxiliary DC supply voltage inuence on functionality during operation
Dependence on Reference value Within nominal
range
Inuence
Ripple, in DC auxiliary voltage
Operative range
max. 2%
Full wave rectified
15% of EL 0.01%/%
Auxiliary voltage dependence, operate
value
±20% of EL 0.01%/%
Interrupted auxiliary DC voltage
24-60 V DC ± 20%
100-250 V DC ±20%
Interruption
interval
0–50 ms
No restart
0–∞ s Correct behaviour at power down
Restart time < 300 s
Table 27. Frequency inuence (reference standard: IEC 60255–1)
Dependence on
Within nominal range Inuence
Frequency dependence, operate value f
r
±2.5 Hz for 50 Hz
f
r
±3.0 Hz for 60 Hz
±1.0%/Hz
Harmonic frequency dependence (20% content)
2
nd
, 3
rd
and 5
th
harmonic of f
r
±2.0%
Harmonic frequency dependence for high impedance differential
protection (10% content)
2
nd
, 3rd and 5
th
harmonic of f
r
±10.0%
Harmonic frequency dependence for overcurrent protection
2
nd
, 3
rd
and 5
th
harmonic of f
r
±3.0%
Type tests according to standards
IP15778-1 v1
M16706-1 v10
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
ABB 55

Table of Contents

Other manuals for ABB rec670

Related product manuals