ABB rec670 - Frequency Protection Status

ABB rec670
138 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
GUID-E2EA8017-BB4B-48B0-BEDA-E71FEE353774 v5
Table 63. Fuse failure supervision VDSPVC
Function Range or value Accuracy
Operate value, block of main fuse failure (10.0-80.0)% of UBase ±0.5% of Ur
Reset ratio <110%
Operate time, block of main fuse failure at 1 x U
r
to 0 Min. = 5 ms
Max. = 15 ms
Reset time, block of main fuse failure at 0 to 1 x U
r
Min. = 15 ms
Max. = 30 ms
Operate value, alarm for pilot fuse failure (10.0-80.0)% of UBase ±0.5% of Ur
Reset ratio <110%
Operate time, alarm for pilot fuse failure at 1 x U
r
to 0 Min. = 5 ms
Max. = 15 ms
Reset time, alarm for pilot fuse failure at 0 to 1 x U
r
Min. = 15 ms
Max. = 30 ms
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
ABB 81