Logic
M12380-1 v12
Table 72. Tripping logic common 3-phase output SMPPTRC
Function Range or value Accuracy
Trip action 3-ph, 1/3-ph, 1/2/3-ph -
Minimum trip pulse length (0.000-60.000) s ±0.2% or ±15 ms whichever is greater
3-pole trip delay (0.020-0.500) s ±0.2% or ±15 ms whichever is greater
Evolving fault delay (0.000-60.000) s ±0.2% or ±15 ms whichever is greater
GUID-1E1A829D-1F26-433A-8813-1F5A6F225418 v1
Table 73. Number of SMAGAPC instances
Function Quantity with cycle time
3 ms 8 ms 100 ms
SMAGAPC 12 - -
Table 74. Number of STARTCOMB instances
Function Quantity with cycle time
3 ms 8 ms 100 ms
STARTCOMB 32 - -
GUID-3AB1EE95-51BF-4CC4-99BD-F4ECDAACB75A v1
Table 75. Number of TMAGAPC instances
Function Quantity with cycle time
3 ms 8 ms 100 ms
TMAGAPC 6 6 -
GUID-A05AF26F-DC98-4E62-B96B-E75D19F20767 v1
Table 76. Number of ALMCALH instances
Function Quantity with cycle time
3 ms 8 ms 100 ms
ALMCALH - - 5
GUID-70B7357D-F467-4CF5-9F73-641A82D334F5 v1
Table 77. Number of WRNCALH instances
Function Quantity with cycle time
3 ms 8 ms 100 ms
WRNCALH - - 5
GUID-EAA43288-01A5-49CF-BF5B-9ABF6DC27D85 v1
Table 78. Number of INDCALH instances
Function Quantity with cycle time
3 ms 8 ms 100 ms
INDCALH - 5 -
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
88 ABB