GUID-B258726E-1129-47C9-94F9-BE634A2085FA v3
Table 105. Elapsed time integrator with limit transgression and overow supervision TEIGAPC
Function Cycle time (ms) Range or value Accuracy
Elapsed time integration 3 0 ~ 999999.9 s ±0.2% or ±20 ms whichever is
greater
8 0 ~ 999999.9 s ±0.2% or ±100 ms whichever is
greater
100 0 ~ 999999.9 s ±0.2% or ±250 ms whichever is
greater
Table 106. Number of TEIGAPC instances
Function
Quantity with cycle time
3 ms 8 ms 100 ms
TEIGAPC 4 4 4
GUID-CEA332FF-838D-42B7-AEFC-C1E87809825E v2
Table 107. Number of INTCOMP instances
Function Quantity with cycle time
3 ms 8 ms 100 ms
INTCOMP 10 10 10
GUID-3FDD7677-1D86-42AD-A545-B66081C49B47 v3
Table 108. Number of REALCOMP instances
Function Quantity with cycle time
3 ms 8 ms 100 ms
REALCOMP 10 10 10
1MRK 511 404-BEN A
Bay control REC670 2.2
Product version: 2.2.1
ABB 93