Loading...
The relay supports the following high accuracy time
synchronization method with a time-stamping resolution of 4 µs
required especially in process bus applications.
PTP (IEEE 1588) v2 with Power Profile
The IEEE 1588 support is included in all variants having a
redundant Ethernet communication module.
IEEE 1588 v2 features
Ordinary Clock with Best Master Clock algorithm
One-step Transparent Clock for Ethernet ring topology
1588 v2 Power Profile
Receive (slave): 1-step/2-step
Transmit (master): 1-step
Layer 2 mapping
Peer to peer delay calculation
Multicast operation
Required accuracy of grandmaster clock is +/-1 µs. The relay
can work as a master clock per BMC algorithm if the external
grandmaster clock is not available for short term.
The IEEE 1588 support is included in all variants having a
redundant Ethernet communication module.
In addition, the relay supports time synchronization via
Modbus, DNP3 and IEC 60870-5-103 serial communication
protocols.
Table 5. Supported station communication interfaces and protocols
Interfaces/Protocols Ethernet Serial
100BASE-TX RJ-45 100BASE-FX LC RS-485 Fiber optic ST
IEC 61850-8-1 - -
IEC 61850-9-2 LE -
MODBUS RTU/ASCII - -
MODBUS TCP/IP - -
DNP3 (serial) - -
DNP3 TCP/IP - -
IEC 60870-5-103 - -
● = Supported
Line Differential Protection and Control
1MRS756500 K
RED615
Product version: 5.0 FP1
24 ABB

Table of Contents