additional local HMI language to the protection relay. The
update tool is activated using PCM600, and it enables multiple
updates of the additional HMI language, thus offering flexible
means for possible future language updates.
Table 104. Tools
Configuration and setting tools Version
PCM600 2.6 (Rollup 20150626) or later
Web browser-based user interface IE 8.0, IE 9.0, IE 10.0 or IE 11.0
RED615 Connectivity Package 5.1 or later
Table 105. Supported functions
Function Web HMI PCM600
Relay parameter setting ● ●
Saving of relay parameter settings in the relay ● ●
Signal monitoring ● ●
Disturbance recorder handling ● ●
Alarm LED viewing ● ●
Access control management ● ●
Relay signal configuration (Signal Matrix) - ●
Modbus® communication configuration (communication management) - ●
DNP3 communication configuration (communication management) - ●
IEC 60870-5-103 communication configuration (communication
management) - ●
Saving of relay parameter settings in the tool - ●
Disturbance record analysis - ●
XRIO parameter export/import - ●
Graphical display configuration - ●
Application configuration - ●
IEC 61850 communication configuration, GOOSE (communication
configuration) - ●
Phasor diagram viewing ● -
Event viewing ● ●
Saving of event data on the user's PC ● ●
Online monitoring - ●
● = Supported
28. Cyber security
The relay supports role based user authentication and
authorization. It can store 2048 audit trail events to a non-
volatile memory. The non-volatile memory is based on a
memory type which does not need battery backup or regular
component exchange to maintain the memory storage. FTP
and Web HMI use TLS encryption with a minimum of 128 bit key
length protecting the data in transit. In this case the used
communication protocols are FTPS and HTTPS. All rear
communication ports and optional protocol services can be
deactivated according to the desired system setup.