Table 17. Protection communication link
Connector Fibre type Wave length Typical max.
length
1)
Permitted path attenuation
2)
LC MM 62.5/125 or 50/125 μm 1300 nm 2 km <8 dB
LC
SM 9/125 μm
3)
1300 nm 20 km <8 dB
1) Maximum length depends on the cable attenuation and quality, the amount of splices and connectors in the path.
2) Maximum allowed attenuation caused by connectors and cable altogether
3) Use single-mode fiber with recommended minimum length of 3 m to connect RED615 to the pilot wire modem RPW600.
Table 18. IRIG-B
Description
Value
IRIG time code format
B004, B005
1)
Isolation 500V 1 min
Modulation Unmodulated
Logic level 5 V TTL
Current consumption <4 mA
Power consumption <20 mW
1) According to the 200-04 IRIG standard
Table 19. Degree of protection of flush-mounted protection relay
Description
Value
Front side IP 54
Rear side, connection terminals IP 20
Table 20. Environmental conditions
Description
Value
Operating temperature range -25...+55ºC (continuous)
Short-time service temperature range
-40...+70ºC (<16h)
1)2)
Relative humidity <93%, non-condensing
Atmospheric pressure 86...106 kPa
Altitude Up to 2000 m
Transport and storage temperature range -40...+85ºC
1) Degradation in MTBF and HMI performance outside the temperature range of -25...+55 ºC
2) For relays with an LC communication interface the maximum operating temperature is +70 ºC
Line Differential Protection and Control
1MRS756500 K
RED615
Product version: 5.0 FP1
28 ABB