EasyManua.ls Logo

ABB RED615 - Dimensions; Power Supply; Energizing Inputs; Technical Data

ABB RED615
72 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
21. Technical data
Table 6. Dimensions
Description Value
Width Frame 177 mm
Case 164 mm
Height Frame 177 mm (4U)
Case 160 mm
Depth 201 mm (153 + 48 mm)
Weight Complete protection relay 4.1 kg
Plug-in unit only 2.1 kg
Table 7. Power supply
Description
Type 1 Type 2
Nominal auxiliary voltage U
n
100, 110, 120, 220, 240 V AC, 50 and 60 Hz 24, 30, 48, 60 V DC
48, 60, 110, 125, 220, 250 V DC
Maximum interruption time in the auxiliary
DC voltage without resetting the relay
50 ms at U
n
Auxiliary voltage variation 38...110% of U
n
(38...264 V AC) 50...120% of U
n
(12...72 V DC)
80...120% of U
n
(38.4...300 V DC)
Start-up threshold 19.2 V DC (24 V DC × 80%)
Burden of auxiliary voltage supply under
quiescent (P
q
)/operating condition
DC <12.0 W (nominal)/<18.0 W (max)
AC <16.0 W (nominal)/<21.0 W (max)
DC <12.0 W (nominal)/<18.0 W (max)
Ripple in the DC auxiliary voltage Max 15% of the DC value (at frequency of 100 Hz)
Fuse type T4A/250 V
Table 8. Energizing inputs
Description
Value
Rated frequency 50/60 Hz
Current inputs Rated current, I
n
0.2/1 A
1/5 A
1)
Thermal withstand capability:
Continuously 4 A 20 A
For 1 s 100 A 500 A
Dynamic current withstand:
Half-wave value 250 A 1250 A
Input impedance <100 mΩ <20 mΩ
Voltage inputs Rated voltage 60...210 V AC
Voltage withstand:
Continuous 240 V AC
For 10 s 360 V AC
Burden at rated voltage <0.05 VA
1) Residual current and/or phase current
Line Differential Protection and Control
1MRS756500 K
RED615
Product version: 5.0 FP1
ABB 25

Table of Contents

Other manuals for ABB RED615

Related product manuals