Table 52. Three-phase overvoltage protection (PHPTOV)
Characteristic Value
Operation accuracy Depending on the frequency of the measured voltage: f
n
 ±2 Hz
±1.5% of the set value or ±0.002 × U
n
Start time
1)2)
 
Minimum Typical Maximum
U
Fault
 = 1.1 × set 
Start value
23 ms 27 ms 31 ms
Reset time Typically 40 ms
Reset ratio Depends of the set 
Relative hysteresis
Retardation time <35 ms
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode
±5.0% of the theoretical value or ±20 ms
3)
Suppression of harmonics DFT: -50 dB at f = n × f
n
, where n = 2, 3, 4, 5,…
1)
Start value
 = 1.0 × U
n
, Voltage before fault = 0.9 × U
n
, f
n
 = 50 Hz, overvoltage in one phase-to-phase with nominal frequency injected from random phase angle, results based on statistical
distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Maximum 
Start value
 = 1.20 × U
n
, 
Start value
 multiples in range of 1.10... 2.00
Table 53. Three-phase overvoltage protection (PHPTOV) main settings
Parameter
Function Value (Range) Step
Start value PHPTOV 0.05...1.60 × U
n
0.01
Time multiplier PHPTOV 0.05...15.00 0.01
Operate delay time PHPTOV 40...300000 ms 10
Operating curve type
1)
PHPTOV Definite or inverse time
Curve type: 5, 15, 17, 18, 19, 20
1) For further reference, see Operation characteristics table
Table 54. Positive-sequence undervoltage protection (PSPTUV)
Characteristic
Value
Operation accuracy Depending on the frequency of the measured voltage: f
n
 ±2 Hz
±1.5% of the set value or ±0.002 × U
n
Start time
1)2)
  Minimum Typical Maximum
U
Fault
 = 0.99 × set 
Start value
U
Fault
 = 0.9 × set 
Start value
52 ms
44 ms
55 ms
47 ms
58 ms
50 ms
Reset time Typically 40 ms
Reset ratio Depends of the set 
Relative hysteresis
Retardation time <35 ms
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Suppression of harmonics DFT: -50 dB at f = n × f
n
, where n = 2, 3, 4, 5,…
1)
Start value
 = 1.0 × U
n
, Positive sequence voltage before fault = 1.1 × U
n
, f
n
 = 50 Hz, positive sequence undervoltage with nominal frequency injected from random phase angle, results based
on statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact