ABB RED670 - Directional Underpower Protection GUPPDUP; Directional Overpower Protection GOPPDOP

ABB RED670
137 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table 56. Stub protection STBPTOC
Function Range or value Accuracy
Operating current (5-2500)% of
IBase
±1.0% of I
r
at I ≤ I
r
±1.0% of I at I > I
r
Reset ratio > 95% at (50-2500)% of
IBase
-
Independent time delay at 0 to 2 x I
set
(0.000-60.000) s
±0.2% or ±30 ms whichever is
greater
Operate time, start at 0 to 2 x I
set
Min. = 10 ms
Max. = 20 ms
-
Reset time, start at 2 to 0 x I
set
Min. = 10 ms
Max. = 20 ms
-
Critical impulse time 10 ms typically at 0 to 2 x I
set
-
Impulse margin time 15 ms typically -
Table 57. Pole discordance protection CCPDSC
Function
Range or value Accuracy
Operate current (0–100)% of
IBase
±1.0% of I
r
Independent time delay between
trip condition and trip signal
(0.000-60.000) s ±0.2% or ± 25 ms whichever is greater
Table 58. Directional underpower protection GUPPDUP
Function
Range or value Accuracy
Power level
for Step 1 and Step 2
(0.0–500.0)% of
SBase
±1.0% of S
r
at S ≤ S
r
±1.0% of S at S > S
r
where
1.732
r r r
S U I= × ×
Characteristic angle
for Step 1 and Step 2
(-180.0–180.0) degrees ±2.0 degrees
Independent time delay to operate for Step 1
and Step 2 at 2 to 0.5 x S
r
and
k
=
0.000
(0.01-6000.00) s ±0.2% or ±40 ms whichever is greater
Table 59. Directional overpower protection GOPPDOP
Function
Range or value Accuracy
Power level
for Step 1 and Step 2
(0.0–500.0)% of SBase
±1.0% of S
r
at S ≤ S
r
±1.0% of S at S > S
r
Characteristic angle
for Step 1 and Step 2
(-180.0–180.0) degrees ±2.0 degrees
Operate time, start at 0.5 to 2 x S
r
and
k
=
0.000
Min. =10 ms
Max. = 25 ms
Reset time, start at 2 to 0.5 x S
r
and
k
=
0.000
Min. = 35 ms
Max. = 55 ms
Independent time delay to operate for Step 1
and Step 2 at 0.5 to 2 x S
r
and
k
=
0.000
(0.01-6000.00) s ±0.2% or ±40 ms whichever is greater
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
ABB 73