EasyManua.ls Logo

ABB RED670 - Measurements CVMMXN; Phase Current Measurement CMMXU; Phase-Phase Voltage Measurement VMMXU

ABB RED670
137 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Monitoring
Table 128. Measurements CVMMXN
Function Range or value Accuracy
Frequency (0.95-1.05) x f
r
±2.0 mHz
Voltage (10 to 300) V
±0.3% of U at U 50 V
±0.2% of U at U> 50 V
Current (0.1-4.0) x I
r
±0.8% of I at 0.1 x I
r
< I < 0.2 x I
r
± 0.5% of I at 0.2 x I
r
< I < 0.5 x I
r
±0.2% of I at 0.5 x I
r
< I < 4.0 x I
r
Active power, P (10 to 300) V
(0.1-4.0) x I
r
±0.5% of S
r
at S 0.5 x S
r
±0.5% of S at S > 0.5 x S
r
(100 to 220) V
(0.5-2.0) x I
r
cos φ< 0.7
±0.2% of P
Reactive power, Q (10 to 300) V
(0.1-4.0) x I
r
±0.5% of S
r
at S 0.5 x S
r
±0.5% of S at S > 0.5 x S
r
(100 to 220) V
(0.5-2.0) x I
r
cos φ> 0.7
±0.2% of Q
Apparent power, S (10 to 300) V
(0.1-4.0) x I
r
±0.5% of S
r
at S 0.5 x S
r
±0.5% of S at S >0.5 x S
r
(100 to 220) V
(0.5-2.0) x I
r
±0.2% of S
Power factor, cos (φ)
(10 to 300) V
(0.1-4.0) x I
r
<0.02
(100 to 220) V
(0.5-2.0) x I
r
<0.01
Table 129. Phase current measurement CMMXU
Function
Range or value Accuracy
Current at symmetrical load (0.1-4.0) × I
r
±0.3% of I
r
at I ≤ 0.5 × I
r
±0.3% of I at I > 0.5 × I
r
Phase angle at symmetrical load (0.1-4.0) × I
r
±1.0 degrees at 0.1 × I
r
< I ≤ 0.5 × I
r
±0.5 degrees at 0.5 × I
r
< I ≤ 4.0 × I
r
Table 130. Phase-phase voltage measurement VMMXU
Function
Range or value Accuracy
Voltage (10 to 300) V ±0.5% of U at U ≤ 50 V
±0.2% of U at U > 50 V
Phase angle (10 to 300) V ±0.5 degrees at U ≤ 50 V
±0.2 degrees at U > 50 V
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
ABB 99

Table of Contents

Other manuals for ABB RED670

Related product manuals