Table 123. Number of IB16 instances
Function Quantity with cycle time
3 ms 8 ms 100 ms
IB16 6 4 8
Table 124. Number of ITBGAPC instances
Function Quantity with cycle time
3 ms 8 ms 100 ms
ITBGAPC 4 4 8
Table 125. Elapsed time integrator with limit transgression and overflow supervision TEIGAPC
Function
Cycle time (ms) Range or value Accuracy
Elapsed time integration 3 0 ~ 999999.9 s ±0.2% or ±20 ms whichever is greater
8 0 ~ 999999.9 s ±0.2% or ±100 ms whichever is
greater
100 0 ~ 999999.9 s ±0.2% or ±250 ms whichever is
greater
Table 126. Number of TEIGAPC instances
Function
Quantity with cycle time
3 ms 8 ms 100 ms
TEIGAPC 4 4 4
Table 127. Running hour-meter TEILGAPC
Function
Range or value Accuracy
Time limit for alarm supervision, tAlarm (0 - 99999.9) hours ±0.1% of set value
Time limit for warning supervision, tWarning (0 - 99999.9) hours ±0.1% of set value
Time limit for overflow supervision Fixed to 99999.9 hours ±0.1%
1MRK 505 346-BEN -
Line differential protection RED670 2.1 IEC
Product version: 2.1
98 ABB