SELGAPC1
SELGAPC1 has inputs from protection relay binary inputs. IN_1...IN_4 are binary
inputs from X100. IN_5...IN_10 can be used while X130 optional card is taken into
use. An always true signal is connected to IN_11. SELGAPC1 outputs are used to
route inputs to different functions. By setting SELGAPC1, binary inputs can be
configured for different purposes.
SELGAPC1
Blocking 1
CCBRBRF1_POSCLOSE
CBXCBR1_POSCLOSE
SELGAPC2_IN_1
CB Closed Position
CB Open Position
DARREC1_CB_POS
CBXCBR1_POSOPEN
SELGAPC2_IN_2
TRPTTRC1/2_
RST_LKOUT
CBXCBR1_ENA_CLOSE
CB Close Enable
DARREC1_CB_READY
External Trip
PROTECTION_BI_SG_3
Setting Group 2
PROTECTION_BI_SG_4
Setting Group 3
ISWGAPC2_IN
Setting Group 4
ISWGAPC1_IN
X120/1-2 BI1
X120/3-2 BI2
X120/4-2 BI3
X130/1-2 BI1
X130/3-2 BI2
X130/4-5 BI3
X130/6-5 BI4
X130/7-8 BI5
X130/9-8 BI6
IN_1
IN_2
IN_3
IN_4
IN_5
IN_6
IN_7
IN_8
IN_9
IN_10
1 Optional binary inputs
X120-BI1
X120-BI2
X120-BI3
X130-BI1
X130-BI2
X130-BI3
X130-BI4
X130-BI5
X130-BI6
1
Always True
OUT_1
OUT_2
OUT_3
OUT_4
OUT_5
OUT_6
OUT_7
OUT_8
OUT_9
OUT_10
OUT_11
OUT_12
TRPTTRC1_RST_LKOUT
TRPTTRC2_RST_LKOUT
DARREC1_RECL_ON
TRPTTRC1_OPERATE
TRPTTRC2_OPERATE
IN_11
X120/5-6 BI4
X120-BI4
Blocking 2
PROTECTION_BI_SG_2
GUID-12D6969A-A486-41A3-853C-534194AD4FA9 V1 EN
Figure 74: SELGAPC1
ISWGAPC1
ISWGAPC1 is used to select which protection functions are to be blocked by changing
ISWGAPC1 parameters. ISWGAPC1 input is routed from SELGAPC1 output
OUT_1 Blocking 1. ISWGAPC1 outputs are connected to the BLOCK inputs of
the protection functions.
1MRS757456 D Section 3
REF611 standardized configurations
REF611 95