Figure 22: Disturbance recorder
All start and operate signals from the protection stages are routed to trigger the
disturbance recorder or alternatively only to be recorded by the disturbance recorder
depending on the parameter settings. Additionally, the selected autoreclose output
signals and the three binary inputs from X120 are also connected. The active setting
group is also to be recorded via SG_1_ACT to SG_6_ACT. The disturbance recorder
triggered signal indication is connected to LED 6.
Table 15: Disturbance recorder binary channel default value
Channel number
Channel ID text Level trigger mode
Binary channel 1 PHLPTOC1_START 1=positive or rising
Binary channel 2 PHHPTOC1_START 1=positive or rising
Binary channel 3 PHHPTOC2_START 1=positive or rising
Binary channel 4 PHIPTOC1_START 1=positive or rising
Binary channel 5 EFHPTOC1_START 1=positive or rising
Binary channel 6 DEFLPDEF1_START 1=positive or rising
Binary channel 7 DEFLPDEF2_START 1=positive or rising
Binary channel 8 DEFHPDEF1_START 1=positive or rising
Binary channel 9 ROVPTOV1_START 1=positive or rising
Table continues on next page
Section 3 1MRS757456 D
REF611 standardized configurations
44 REF611
Application Manual