3.5.4.2  Internal signals
The internal signal group is used to configure logic connections between function
blocks. There are two ISWGAPC instances, one SELGAPC and one OSWGAPC
instance in this group.
ISWGAPC3 is used to configure which protection function enables current multiplier
if inrush is detected by the INRPHAR1 function. ISWGAPC4 is used to configure the
cooperation between the autoreclose function and protection functions. Autoreclose
function DARREC1 can block protection functions according to the application.
SELGAPC2 is used to configure TCS blocking from the circuit breaker open or close
position. OSWGAPC17 is used for connecting switch onto fault function CBPSOF.
The inputs are start signals routed from the protection functions.