ISWGA PC3
PHLPTOC1_ENA_MULT
PHHPTOC1_ENA_MULT
PHHPTOC2_ENA_MULT
PHIPTOC1_ENA_MULT
EFLPTOC1_ENA_MULT
EFLPTOC2_ENA_MULT
EFHPTOC1_ENA_MULT
EFIPTOC1_ENA_MULT
NSPTOC1_ENA_MULT
NSPTOC2_ENA_MULT
T1PTTR1_ENA_MULT
ISWGAPC4
PHLPTOC1_BLOCK
PHHPTOC1_BLOCK
PHHPTOC2_BLOCK
EFLPTOC1_BLOCK
EFLPTOC2_BLOCK
EFHPTOC1_BLOCK
SELGAPC2
TCSSCBR1_BLOCK
TCSSCBR2_BLOCK
SELGAPC1_OUT_2
SELGAPC1_OUT_3
CB Closed Position
CB Open Position
PHLPTOC1_START
PHHPTOC1_START
PHHPTOC2_START
PHIPTOC1_START
EFLPTOC1_START
EFLPTOC2_START
EFHPTOC1_START
EFIPTOC1_START
NSPTOC1_START
NSPTOC2_START
PDNSPTOC1_START
T1PTTR1_START
OSWGAPC17
Start
DLYD
CBPSOF1_INIT
GUID-4571B98B-EB9A-45A4-A4B4-6AC63C16D01C V2 EN
Figure 77: Internal signal
ISWGAPC3
ISWGAPC3 input is used to configure which protection function enables current
multiplier while inrush is detected by INRPHAR1 by changing the ISWGAPC3
parameters. ISWGAPC3 input is routed from INRPHAR1 output BLK2H.
ISWGAPC3 outputs are connected to the ENA_MULT inputs of the protection
functions.
Section 3 1MRS757456 D
REF611 standardized configurations
98 REF611
Application Manual