closing the circuit breaker, TCSSCBR2 needs to be blocked by the circuit breaker
close position (OUT_2 connection=IN_1).
SELGAPC2
IN_1
IN_2
OUT_1
OUT_2
TCSSCBR1_BLOCK
TCSSCBR2_BLOCK
SELGAPC1_OUT_2
SELGAPC1_OUT_3
CB Closed Position
CB Open Position
GUID-D390241C-1F0F-4AE7-A803-86931E1E0BEF V1 EN
Figure 80: SELGAPC2
OSWGAPC17
OSWGAPC17 is used to route the protection function start signals to the
StartDLYD input of the switch onto fault function CBPSOF. CBPSOF provides an
instantaneous trip or a time delayed trip when closing the breaker while a fault exists.
OSWGAPC17 output is connected to CBPSOF function indicating the detected fault.
OSWGAPC17
IN_1
IN_2
IN_3
IN_4
IN_5
IN_6
IN_7
IN_8
IN_9
IN_10
IN_11
IN_12
OUT
EFHPTOC1_START
EFLPTOC2_START
NSPPTOC2_START
PDNSPTOC1_START
T1PTTR1_START
PHLPTOC1_START
PHIPTOC1_START
EFHPTOC1_START
EFIPTOC1_START
NSPPTOC1_START
PHHPTOC2_START
PHHPTOC1_START
Start DLYD
CBPSOF1_INIT
GUID-702BA11C-5E0A-4247-942E-76CC27063BB2 V1 EN
Figure 81: OSWGAPC17
Section 3 1MRS757456 D
REF611 standardized configurations
100 REF611
Application Manual