GUID-FB8E7A93-E98A-4968-B8C6-FBD091F5E635 V2 EN
Figure 106: Overcurrent protection
Four overcurrent stages are offered for overcurrent and short-circuit protection. The
instantaneous stage PHIPTOC1 can be blocked by energizing the binary input
(X120:1-2). The inrush detection block’s INRPHAR1 output BLK2H enables either
blocking the function or multiplying the active settings for any of the described
protection function blocks.
All operate signals are connected to the Master Trip and to the alarm LED 1.
1MRS757456 D Section 3
REF611 standardized configurations
REF611 125
Application Manual