autoreclose function DARREC1 can block protection functions according to the
application. SELGAPC2 is used to configure TCS blocking from the circuit breaker
open or close position. OSWGAPC17 is used for connecting switch onto fault
function CBPSOF. The inputs are start signals routed from the protection functions.
GUID-895B4A93-7066-45C6-9EB1-680320A07FC6 V2 EN
Figure 123: Internal signal
ISWGAPC3
ISWGAPC3 input is used to configure which protection function enables current
multiplier while inrush is detected by INRPHAR1 by changing the ISWGAPC3
parameters. ISWGAPC3 input is routed from INRPHAR1 output BLK2H.
ISWGAPC3 outputs are connected to ENA_MULT of the protection functions.
Section 3 1MRS757456 D
REF611 standardized configurations
142 REF611
Application Manual