Table 7: Audit trail events
Audit trail event Description
Configuration change Configuration files changed
Firmware change Firmware changed
Firmware change fail Firmware change failed
Attached to retrofit test case Unit has been attached to retrofit case
Removed from retrofit test case Removed from retrofit test case
Setting group remote User changed setting group remotely
Setting group local User changed setting group locally
Control remote DPC object control remote
Control local DPC object control local
Test on Test mode on
Test off Test mode off
Reset trips Reset latched trips (TRPPTRC*)
Setting commit Settings have been changed
Time change Time changed directly by the user. Note that this is not used
when the protection relay is synchronised properly by the
appropriate protocol (SNTP, IRIG-B, IEEE 1588 v2).
View audit log
Administrator accessed audit trail
Login Successful login from IEC 61850-8-1 (MMS), WHMI, FTP or
LHMI.
Logout Successful logout from IEC 61850-8-1 (MMS), WHMI, FTP or
LHMI.
Password change Password changed
Firmware reset Reset issued by user or tool
Audit overflow Too many audit events in the time period
Violation remote Unsuccessful login attempt from IEC 61850-8-1 (MMS),
WHMI, FTP or LHMI.
Violation local Unsuccessful login attempt from IEC 61850-8-1 (MMS),
WHMI, FTP or LHMI.
PCM600 Event Viewer can be used to view the audit trail events and process related
events. Audit trail events are visible through dedicated Security events view. Since
only the administrator has the right to read audit trail, authorization must be used in
PCM600. The audit trail cannot be reset, but PCM600 Event Viewer can filter data.
Audit trail events can be configured to be visible also in LHMI/WHMI Event list
together with process related events.
To expose the audit trail events through Event list, define the
Authority logging level parameter via Configuration/
Authorization/Security. This exposes audit trail events to all users.
1MRS757456 D Section 2
REF611 overview
REF611 21
Application Manual

Table of Contents

Other manuals for ABB REF611

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB REF611 and is the answer not in the manual?

ABB REF611 Specifications

General IconGeneral
BrandABB
ModelREF611
CategoryProtection Device
LanguageEnglish

Related product manuals