LED 3
UNBALANCE PROTECTION
NSPTOC1
I
2
>(1)
46(1)
BLOCK START
OPERATE3I
ENA_MULT
NSPTOC2
I
2
>(2)
46(2)
BLOCK START
OPERATE
3I
ENA_MULT
OSWGAPC10
OR
OUT
IN_13
IN_14
IN_15
SELGAPC4
IN_12
OUT_3
PDNSPTOC1
I
2
/I
1
(1)
46PD(1)
BLOCK
START
OPERATE
3I
GUID-A367FC04-F391-48E9-9CBF-599AC625C7FF V1 EN
Figure 19: Unbalance protection
Two negative-sequence overcurrent stages NSPTOC1 and NSPTOC2 and one phase
discontinuity stage PDNPSTOC1 are offered for unbalance protection. The phase
discontinuity protection PDNPSTOC1 provides protection for interruptions in the
normal three-phase load supply, for example, in downed conductor situations.
The operate signals of these unbalance protections are connected to the Master Trip
and to alarm LED 3.