DARREC1_OPEN_CB are connected directly to the output contact PO3
(X100:15-19).
TRPPTRC1 and 2 provide the lockout/latching function, event generation and the trip
signal duration setting. One binary input through SELGAPC1 can be connected to the
RST_LKOUT input of the Master Trip. If the lockout operation mode is selected, it is
used to enable external reset.
GUID-1093EFA7-FA5F-4711-BF03-2B30C553BD72 V2 EN
Figure 25: Circuit breaker control
The ENA_CLOSE input, which enables the closing of the circuit breaker, is
interlocked by two master trip signals. Any one trip will block the breaker from
closing. An always true signal is also connected to ENA_CLOSE via SELGAPC1 by
default. The open operation is always enabled.
Section 3 1MRS757456 D
REF611 standardized configurations
48 REF611
Application Manual