ISWGAPC3 is used to configure which protection function enables the current
multiplier if the INRPHAR1 function detects inrush. ISWGAPC4 is used to configure
the cooperation between the autoreclose function and the protection functions. The
autoreclose function DARREC1 can block protection functions according to the
application. SELGAPC2 is used to configure TCS blocking from the circuit breaker
open or close position. OSWGAPC17 is used for connecting switch onto fault
function CBPSOF. The inputs are start signals routed from the protection functions.
GUID-A717CE52-5F4C-40C4-BF71-FBFCB900179B V2 EN
Figure 33: Internal signal
ISWGAPC3
ISWGAPC3 input is used to configure which protection function enables current
multiplier while inrush is detected by INRPHAR1, by changing the ISWGAPC3
parameters. ISWGAPC3 input is routed from INRPHAR1 output BLK2H.
ISWGAPC3 outputs are connected to the ENA_MULT inputs of the protection
functions.