Figure 65: Thermal overload and circuit-breaker failure protection
The thermal overload protection T1PTTR1 provides indication on overload
situations. LED 4 is used for the thermal overload protection alarm indication.
The circuit-breaker failure protection CCBRBRF1 is initiated via the start input by a
number of different protection stages in the protection relay. CCBRBRF1 offers
different operating modes associated with the circuit-breaker position and the
measured phase and residual currents. CCBRBRF1 has two operating outputs:
TRRET and TRBU. The TRRET operate output is used for retripping its own circuit
breaker through Master Trip 2. The TRBU output is used to give a backup trip to the
circuit-breaker feeding upstream. For this purpose, the TRBU operate output signal is
connected to the output PO2 (X100:8-9). LED 8 is used for the backup (TRBU) operate
indication.