SELGAPC1
Blocking 1
CBXCBR1_POSCLOSE
SELGAPC2_IN_1
CB Closed Position
CB Open Position
CBXCBR1_POSOPEN
SELGAPC2_IN_2
TRPPTRC1/2_RST
_LKOUT
CBXCBR1_ENA_CLOSE
CB Close Enable
External Trip
PROTECTION_BI_SG_2
Setting Group 2
PROTECTION_BI_SG_3
Setting Group 3
ISWGAPC1_IN
X130/1-2 BI1
X130/3-4 BI2
X130/5-6 BI3
X130/7-8 BI4
IN_1
IN_2
IN_3
IN_4
IN_5
TRPTTRC1_OPERATE
X130-BI1
X130-BI2
X130-BI3
X130-BI4
Always True
OUT_1
OUT_2
OUT_3
OUT_4
OUT_5
OUT_6
OUT_7
OUT_8
OUT_9
OUT_10
OUT_11
TRPTTRC1_RST_LKOUT
TRPTTRC2_RST_LKOUT
PROTECTION_BI_SG_4
Setting Group 4
Blocking 2
ISWGAPC2_IN
BUS_VT_MCB_
OPEN
B
U
S
_
V
T
_
M
C
B
_
O
P
E
N
_
A
L
A
R
M
GUID-80A08942-C2E5-48CB-94C3-2A803058F830 V2 EN
Figure 27: SELGAPC1
ISWGAPC1
ISWGAPC1 is used to select the protection functions to be blocked by changing the
ISWGAPC1 parameters. ISWGAPC1 input is routed from SELGAPC1 output
OUT_1 Blocking 1. ISWGAPC1 outputs are connected to the BLOCK inputs of
the protection functions.
Section 3 1MRS758335 B
REU611 standardized configuration
46 REU611
Application Manual