Description HR/IR address
(.bit)
DI/Coil bit
address
Writeable Value range Comment
Trip signal from element 46 CD 419.01 34
Trip signal from element 46R 419.02 35 0/1 1 = activated
Trip signal from element 46R CD 419.03 36
CBFAIL 419.04 37 0/1 1 = activated
CBFAIL CD 419.05 38
PO1 419.06 39 0/1 1 = activated
PO1 CD 419.07 40
PO2 419.08 41 0/1 1 = activated
PO2 CD 419.09 42
PO3 419.10 43 0/1 1 = activated
PO3 CD 419.11 44
SO1 419.12 45 0/1 1 = activated
SO1 CD 419.13 46
SO2 419.14 47 0/1 1 = activated
SO2 CD 419.15 48
DI1 420.00 49 0/1 1 = activated
DI1 CD 420.01 50
DI2 420.02 51 0/1 1 = activated
DI2 CD 420.03 52
DI3 420.04 53 0/1 1 = activated
DI3 CD 420.05 54
DI4 420.06 55 0/1 1 = activated
DI4 CD 420.07 56
DI5 420.08 57 0/1 1 = activated
DI5 CD 420.09 58
Alarm signal from element 49/38-1 420.10 59 0/1 1 = activated
Alarm signal from element 49/38-1 CD 420.11 60
Trip signal from element 49/38-1 420.12 61 0/1 1 = activated
Trip signal from element 49/38-1 CD 420.13 62
Alarm signal from element 49/38-2 420.14 63 0/1 1 = activated
Alarm signal from element 49/38-2 CD 420.15 64
Trip signal from element 49/38-2 421.00 65 0/1 1 = activated
Trip signal from element 49/38-2 CD 421.01 66
Disturbance recorder 421.02 67 0/1 1 = triggered
0 = cleared
Disturbance recorder CD 421.03 68
HMI Setting password 421.04 69 0/1 1 = opened
0 = closed
HMI Setting password CD 421.05 70
IRF 421.06 71 0/1 1 = activated
IRF CD 421.07 72
Warning 421.08 73 0/1 1 = activated
Warning CD 421.09 74
84
REM 610REM 610
Motor Protection Relay
Technical Reference Manual - ANSI Version
1MRS755537