Description HR/IR address
(.bit)
DI/Coil bit
address
Writeable Value range Comment
Emergency start 421.10 75 0/1 1 = activated
Emergency start CD 421.11 76
HMI Communication password 421.12 77 0/1 1 = opened
0 = closed
HMI Communication password CD 421.13 78
a)
The thermal restart disable level is exceeded, the start-up time counter is full or the external restart disable signal is active.
Table 5.1.14.1.-9 Mapping of Modbus data: recorded data
Description HR/IR address
(.bit)
DI/Coil bit
address
Writeable Value range Comment
Fault record 601...633 See Structure 2
Event record 671...679 See Structure 3
Table 5.1.14.1.-10 Mapping of Modbus data: relay identification
Description HR/IR address
(.bit)
DI/Coil bit
address
Writeable Value range Comment
Type designation of the relay 701...708 ASCII chars, 2
chars/register
Table 5.1.14.1.-11 Mapping of Modbus data: real-time clock
Description HR/IR address
(.bit)
DI/Coil bit
address
Writeable Value range Comment
Time reading and setting 721...727 W See Structure 4
Table 5.1.14.1.-12 Mapping of Modbus data: additional analog data
Description HR/IR address
(.bit)
DI/Coil bit
address
Writeable Value range Comment
Maximum phase current after motor
start up
801 0...5000 0...50 x FLA
Maximum ground-fault current after
motor start up
802 0...8000 0...800.0% I
n
(CT)
Minimum phase current after motor
start up
803 0...5000 0...50 x FLA
a)
Minimum ground-fault current after
motor start up
804 0...8000 0...800.0% I
n
(CT)
b)
One-minute demand value 805 0...5000 0...50 x FLA
Demand value during the specified
time range
806 0...5000 0...50 x FLA
Maximum one-minute demand value
during the specified time range
807 0...5000 0...50 x FLA
Thermal level 808 0...106 %
Cumulative start-up time counter 809 0...999 Seconds
Time to next possible motor start up 810 0...999 Minutes
Motor running time 811 0...999 x 100 h
Maximum phase current during motor
start up
812 0...5000 0...50 x FLA
Element/phase which caused the trip 813 0...65535 See Table 5.1.15.-
2
Motor Protection Relay
Technical Reference Manual - ANSI Version