Table 19. Electromagnetic compatibility tests
e EMC immunity test level meets the requirements listed below:
Description Type test value Reference
1 MHz burst disturbance test, class III:
• Common mode
• Di erential mode
2.5 kV
1.0 kV
According to IEC 61000-4-18 and
IEC 60255-22-1, level 3
Electrostatic discharge test
• Contact discharge
• Air discharge
6 kV
8 kV
According to IEC 61000-4-2,
IEC 60255-22-2, level 3
Radio frequency interference tests:
Conducted, common mode
• Radiated, amplitude-modulated
• Radiated, pulse-modulated
10 V (emf ), f = 150
kHz...80 MHz
10 V/m (rms),
f=80...1000 MHz and
f=1.4...2.7 GHz
10 V/m, f=900 MHz
According to IEC 61000-4-6 and
IEC 60255-22-6, level 3
According to IEC 61000-4-3 and
IEC 60255-22-3, level 3
According to the ENV 50204 and
IEC 60255-22-3, level 3
Fast transient disturbance tests:
• Signal outputs, binary inputs, IRF
• Other ports
2 kV
4 kV
According to IEC 61000-4-4 and
IEC 60255-22-4, class B
Surge immunity test:
• Binary inputs
• Communication
• Other ports
2 kV, line-to-earth
1kV, line-to-line
1 kV, line-to-earth
4 kV, line-to-earth
2 kV, line-to-line
According to IEC 61000-4-5 and
IEC 60255-22-5, level 4/3
Power frequency (50 Hz) magnetic  eld:
• Continuous 300 A/m
According to IEC 61000-4-8, level 5
Power frequency immunity test:
• Common mode
• Di erential mode
300 V rms
150 V rms
According to IEC 60255-22-7, class
A
Voltage dips and short interruptions 30%/10 ms
60%/100 ms
60%/1000 ms
>95%/5000 ms
According to IEC 61000-4-11