ABB 19
Motor Protection
REM615 ANSI
Product Version 2.0
1MAC251744 -PG Rev. A
Issued: 03.01.2010
Table 20. Insulation tests
Description Value
Dielectric tests: According to IEC 60255-5
• Test voltage 2 kV, 50 Hz, 1 min
500 V, 50 Hz, 1min,
communication
Impulse voltage test: According to IEC 60255-5
• Test voltage 5 kV, unipolar impulses, waveform
1.2/50 μs, source energy 0.5 J
1 kV, unipolar impulses, waveform
1.2/50 μs, source energy 0.5 J, com-
munication
Insulation resistance measurements According to IEC 60255-5
• Isolation resistance >100 MΩ, 500 V DC
Protective bonding resistance
• Resistance
According to IEC 60255-27
<0.1 Ω (60 s)
Table 21. Mechanical tests
Description Value
Vibration tests (sinusoidal) According to IEC 60255-21-1,
class 2
Shock and bump test According to IEC 60255-21-2,
class 2
Table 19. Electromagnetic compatibility tests (continued)
e EMC immunity test level meets the requirements listed below:
Description Value
Electromagnetic emission tests:
• Conducted, RF emission (mains terminal)
0.15...0.50 MHz
0.5...30 MHz
• Radiated RF emission
0...230 MHz
230...1000 MHz
According to the EN 55011,
class A and IEC60255-25
< 79 dB(μV) quasi peak
< 66 dB(μV) average
< 73 dB(μV) quasi peak
< 60 dB(μV) average
< 40 dB(μV/m) quasi peak,
measured at 10 m distance
< 47 dB(μV/m) quasi peak,
measured at 10 m distance
Table 22. EMC Compliance
Description Reference
EMC directive 2004/108/EC
Standard EN 50263 (2000)
EN 60255-26 (2007)