Loading...
IEC15000430-2-en.vsdx
RLd
R
jX
P1
P2
P3
P4
P5
P6
P7
P8
Z1CircleStart
RLd
LineAng
ArgLd
(
)
(
)
IEC15000430 V2 EN-US
Figure 14: Proposed test points for phase-to-phase loop of circular
characteristic in solidly earthed system
Table 16: Test points for phase-to-phase loop of circular characteristic
Test point
R X Comment
P1
Z1CircleStart
cos(
LineAng
)
Z1CircleStart
sin(
LineAng
)
P2 0.8 ∗
Z1CircleStart
cos(
ArgLd
)
0.8 ∗
Z1CircleStart
sin(
ArgLd
)
P3 RLd 0
P4 -
Z1CircleStart
cos(
LineAng
)
-
Z1CircleStart
sin(
LineAng
)
P5 -0.8 ∗
Z1CircleStart
cos(
ArgLd
)
-0.8 ∗
Z1CircleStart
sin(
ArgLd
)
P6 -RLd 0
P7
Z1CircleStart
cos(
ArgLd
)
-
Z1CircleStart
sin(
ArgLd
)
P8 -
Z1CircleStart
cos(
ArgLd
)
Z1CircleStart
sin(
ArgLd
)
1MRK 506 377-UEN C Section 10
Testing functionality by secondary injection
Railway application RER670 2.2 IEC 85
Commissioning manual

Table of Contents