4.1.1.11  Technical data
Table 169: PHxPTOC Technical data
Characteristic Value
Operation accuracy   Depending on the frequency of the current
measured: f
n
 ±2 Hz
PHLPTOC
±1.5% of the set value or ±0.002 x I
n
PHHPTOC
and
PHIPTOC
±1.5% of set value or ±0.002 x I
n
(at currents in the range of 0.1…10 x I
n
)
±5.0% of the set value
(at currents in the range of 10…40 x I
n
)
Start time 
1)2)
  Minimum Typical Maximum
PHIPTOC:
I
Fault
 = 2 x set 
Start
value
I
Fault
 = 10 x set 
Start
value
 
16 ms
 
11 ms
 
19 ms
 
12 ms
 
23 ms
 
14 ms
PHHPTOC and
PHLPTOC:
I
Fault
 = 2 x set 
Start
value
 
 
22 ms
 
 
24 ms
 
 
25 ms
Reset time < 40 ms
Reset ratio Typical 0.96
Retardation time < 30 ms
Operate time accuracy in definite time mode ±1.0% of the set value or ±20 ms
Operate time accuracy in inverse time mode
±5.0% of the theoretical value or ±20 ms 
3)
Suppression of harmonics RMS: No suppression
DFT: -50 dB at f = n x f
n
, where n = 2, 3, 4, 5,…
Peak-to-Peak: No suppression
P-to-P+backup: No suppression
1)
Measurement mode
 = default (depends on stage), current before fault = 0.0 x I
n
, f
n
 = 50 Hz, fault
current in one phase with nominal frequency injected from random phase angle, results based on
statistical distribution of 1000 measurements
2) Includes the delay of the signal output contact
3) Maximum 
Start value
 = 2.5 x I
n
, 
Start value
 multiples in range of 1.5 to 20
4.1.1.12  Technical revision history
Table 170: PHIPTOC Technical revision history
Technical revision
Change
B Minimum and default values changed to 40 ms
for the 
Operate delay time
 setting.
C Minimum and default values changed to 20 ms
for the 
Operate delay time
 setting.
Minimum value changed to 1.00 x I
n
 for the 
Start
value
 setting.
Section 4 1YHT530004D05 D
Protection functions
156 615 series
Technical Manual