local time. As no reboot is necessary, the time synchronization starts immediately
after the IRIG-B sync source is selected and the IRIG-B signal source is connected.
ABB has tested the IRIG-B with the following clock masters:
Tekron TTM01 GPS clock with IRIG-B output
Meinberg TCG511 controlled by GPS167
Datum ET6000L
Arbiter Systems 1088B
IRIG-B time synchronization requires a COM card with an IRIG-B
input.
When using line differential communication between RED615 IEDs, the time
synchronization messages can be received from the other line end IED within the
protection telegrams. The IED begins to synchronize its real-time clock with the
remote end IEDs time if the Line differential time synchronization source is
selected. This does not affect the protection synchronization used in the line
differential protection or the selection of the remote end IEDs time synchronization
method.
[1]
3.6 Parameter setting groups
3.6.1 Function block
GUID-76F71815-D82D-4D81-BCFE-28AF2D56391A V1 EN
Figure 15: Function block
3.6.2 Functionality
The IED supports six setting groups. Each setting group contains parameters
categorized as group settings inside application functions. The customer can
change the active setting group at run time.
The active setting group can be changed by a parameter or via binary inputs
depending on the mode selected with the Configuration/Setting Group/SG
operation mode setting.
[1] The line differential protection is available only in RED615.
1YHT530004D05 D Section 3
Basic functions
615 series 71
Technical Manual

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB RET615 D and is the answer not in the manual?

ABB RET615 D Specifications

General IconGeneral
TypeFeeder Protection Relay
Rated Frequency50/60 Hz
Rated Voltage100-240 V AC/DC
Communication ProtocolsIEC 61850, Modbus, DNP3
Input Voltage24-250 V DC
Operating Temperature Range-25°C to +55°C
Enclosure ClassIP54
MountingFlush mounting