Programming
34
Note: The new settings take effect only when the module is
powered up the next time or when the module receives a ‘Fieldbus
Adapter parameter refresh’ command from the drive.
Data transfer rates supported
The RPBA-01 supports the following PROFIBUS communication
speeds: 9.6 kbit/s, 19.2 kbit/s, 45.45 kbit/s, 93.75 kbit/s, 187.5
kbit/s, 500 kbit/s, 1.5 Mbit/s, 3 Mbit/s, 6 Mbit/s, 12 Mbit/s.
The RPBA-01 automatically detects the communication speed
and PPO-type used.
Table 5. The RPBA-01 configuration parameters.
Par.
no.
Parameter name Alternative settings Default
setting
1 MODULE TYPE (Read-only) PROFIBUS DP
2
NODE ADDRESS
0 to 126 3
3 BAUD RATE
1)
(12000) 12 Mbit/s; (6000) 6 Mbit/s;
(3000) 3 Mbit/s; (1500) 1.5 Mbit/s;
(500) 500 kbit/s; (187) 187.5 kbit/s;
(93) 93.75 kbit/s; (45) 45.45 kbit/s;
(19) 19.2 kbit/s; (9) 9.6 kbit/s;
(Read-only)
1500
4 PPO-TYPE
1)
(1) PPO 1; (2) PPO 2; (3) PPO 3;
(4) PPO 4; (5) PPO 5; (6) PPO 6;
(Read-only)
(1) PPO 1
5 PZD3 OUT 0 to 32767 with format xxyy, where
xx = Parameter Group and
yy = Parameter Index.
See description below.
0
6 PZD3 IN See PZD3 OUT above 0
7 PZD4 OUT See PZD3 OUT above 0
8 PZD4 IN See PZD3 OUT above 0
... ...