DP-V0 communication
60
Example 6: Configuring the process data written to the drive
PROFIBUS parameter 915 can be used to define which data is
written cyclically to a drive parameter as application-specific
process data.
In the example below, the value of drive parameter
12.02 CONSTANT SPEED 1 (4B2h) is selected to be taken from
PZD3. The parameter will continue to be updated with the
contents of PZD3 in each Request frame until a different selection
is made.
Subindex (IND) defines which process data word the required
data is taken from. Parameter Value selects the drive parameter to
which that word is mapped.
Subsequently, the contents of PZD3 in each Request frame are
written to drive parameter 12.02 CONSTANT SPEED 1 until a
different selection is made.
Req73930300000004B2047F34150000000000000000
Resp 43 93 03 00 00 00 04 B2 03 37 34 15 00 00 00 00 00 00 00 00
Parameter Value (1202 Dec)
CW REF
Parameter Number (915 Dec)
Request (Change parameter value [array])
Subindex (03 = PZD3)*
PZD3 PZD4 PZD5 PZD6
SW ACT
*2nd byte reserved
PZD3 PZD4 PZD5 PZD6
Parameter Value (1202 Dec)
Parameter Number (915 Dec)
Response (Transfer parameter value [array])
Subindex (03 = PZD3)*