DP-V0 communication
61
Example 7: Configuring the process data read from the drive
PROFIBUS Parameter No. 916 can be used to define which data
is read cyclically from the drive as application-specific process
data.
In the example below, drive parameter 1.04 CURRENT (68h) is
selected to be transmitted by the drive as PZD3. The selection is
in force until it is superseded by another selection.
Subindex (IND) defines which process data word the required
data is transmitted in, and Parameter Value defines which drive
parameter is mapped to that word.
Subsequent response frames:
Req7394030000000068047F34150000000000000000
Resp 43 94 03 00 00 00 00 68 03 37 34 15 00 00 00 00 00 00 00 00
Resp xx xx xx xx xx xx xx xx xx xx xx xx 00 0B xx xx xx xx xx xx
Parameter Value (104 Dec)
CW REF
Parameter Number (916 Dec)
Request (Change parameter value [array])
Subindex (03 = PZD3)*
PZD3 PZD4 PZD5 PZD6
SW ACT
*2nd byte reserved
PZD3 PZD4 PZD5 PZD6
Parameter Value (104 Dec)
Parameter Number (916 Dec)
Response (Transfer parameter value [array])
Subindex (03 = PZD3)*
PZD3 (Value of Drive Parameter 1.04)