DP-V1 communication
75
Table 12. The Status Word (PROFIBUS Parameter 968). The
upper case boldface text refers to the states shown in Figure 13.
Bit Name Value STATE/Description
0 RDY_ON 1 READY TO SWITCH ON
0 NOT READY TO SWITCH ON
1 RDY_RUN 1 READY TO OPERATE
0 OFF1 ACTIVE
2 RDY_REF 1 ENABLE OPERATION
0 DISABLE OPERATION
3 TRIPPED 1 FAULT
0No fault
4 OFF_2_STA 1 OFF2 inactive
0 OFF2 ACTIVE
5 OFF_3_STA 1 OFF3 inactive
0 OFF3 ACTIVE
6 SWC_ON_INHIB 1 SWITCH-ON INHIBIT ACTIVE
0 SWITCH-ON INHIBIT NOT ACTIVE
7 ALARM 1 Warning/Alarm
0 No Warning/Alarm
8 AT_SETPOINT 1 OPERATING. Actual value equals reference value
(i.e. is within tolerance limits)
0 Actual value differs from reference value
(= is outside tolerance limits)
9 REMOTE 1 Drive control location: REMOTE
0 Drive control location: LOCAL
10 ABOVE_LIMIT 1 Actual frequency or speed value equals or is greater
than supervision limit.
0 Actual frequency or speed value is within supervision
limit.