• The following limitations must be considered for PR123/P relays with software releases
prior to 1.10:
3.8 Information
This menu displays information about the relay and circuit-breaker.
The menu can also be accessed so as to download information from the PR010/T unit to the PC.
The download requires a dedicated procedure. It uis not available for PR232/P.
3.8.1 Download
A file is created containing a first group of information, stored in the non-volatile memory of the
PR010/T unit. You will be asked to enter certain information for heading the report, namely the
date, time, operator's name and CB Serial Number.
This file can be diwnloaded into a PC in the same way as the normal test reports are downloaded.
The Download info 2 command can also be used to download a group of useful information.
Vacant space must be created in the memory before the data are stored and downloaded into the
PC.
Only one group of information can be stored at a time by freeing space (deleting reports) before
storing aother group. For example, if you wish to download all the information (download info 1
nand download info 2):
1. Delete any reports to free sufficient space in the non-volatile memory
2. Perform download 1
3. Download the corresponding file into the PC
4. Delete reports
5. Perform download 2
6. Download the corresponding file into the PC
7. Delete reports to free sufficient space for the report of a next test
1. Startup time protection S: 0.1s Time 1.5s step 0.01s
2. Startup time protection S2: 0.1s Time 1.5s step 0.01s
3. Startup time protection G: 0.1s Time 1.5s step 0.01s
4. Startup time protection Gext: 0.1s Time 1.5s step 0.01s
5. Startup time protection D: 0.1s Time 1.5s step 0.01s
6. Startup current activation threshold not available
7. Threshold protection U: 5% th 90% step 5%
8. Minimum custom datalogger enabling time not available