ABB | SACE Tmax XT
External accessories | 7 - Ekip Com Modbus TCP141 | © 2019 ABB | 1SDH002039A1002 - ECN000093027 - Rev. A
Connections
For references about the connection and terminals, please consult document 1SDM000005A1001; a cable
of the Class 6 S/FTP type (Class 6 with double screening S/FTP) must be used for the communication bus.
To connect the module to Ekip Supply and Ekip Cartridge, please consult document 1SDH002009A1503.
Power supply
Ekip Com Modbus TCP is supplied directly by the Ekip Supply module to which it is connected.
NOTE: communication between Ekip Touch and the module is interrupted in the absence of
auxiliary power supply
Interface
the module has three signaling leds:
1
2
Figure 46
LEDs Description
Power
Signals the on status and correct communication with Ekip Touch:
• off: module off
• on steady or flashing synchronized with the Power led of Ekip Touch: module on and
communication with Trip unit present.
• flashing not synchronized with the Power led of Ekip Touch (2 fast flashes per
second): module on and communication with Trip unit absent.
Link (1)
Indicates the communication state:
• off: incorrect connection, signal absent.
• on steady: connection correct
Activity (2)
Indicates the communication state:
• off: no activity on line
• flashing: activity on line present (receiving and/or transmitting)
Mode
The two operating modes available can be configured via the menu:
Mode Description
Modbus TCP
Information and commands are managed by single requests/queries according to
Modbus TCP protocol rules and mapping (see System Interface)
HTTP Server
Information and commands are available in a web page, which can be accessed via
a browser by entering the IP Address of the module as the address.
The page has a login window where the user is requested to enter the same user
password as the one requested on the display for editing parameters.