114 | © 2019 ABB | 1SDH002039A1002 - ECN000093027 - Rev. A Settings | 1 - Main settings
Settings
1 - Main settings
Foreword
All the following parameters are available either directly, or from the Settings menu, in the conditions
established by Ekip Touch on the basis of the version and configuration described.
To correctly address parameters which are present in the menu but not described below:
Circuit-breaker: Hardware Trip, T Protection, Neutral Protection
Phase sequence
Monitor time
Power Controller
Load Shedding
Network Analyzer
Datalogger
Dual Set
Functions
please consult the Settings menu overview (page 33).
WARNING! changes to the settings must be made in the absence of protection alarms
Configuration
The Circuit breaker-Configuration menu, allowing the presence of the External neutral sensor to be activated,
is available for the 3P CB (page 200).
Activation of the configuration with External neutral (3P + N) enables:
histograms of phase Ne in the Histograms page
neutral current measurements
submenu for configuring the Neutral protection (Neutral Protection)
neutral current recording in the case of TRIP
With 3P CB, the parameter is set by default as: 3P.
Line frequency
Frequency adjustment is performed to set the installation frequency; the choice is between 50 Hz and 60 Hz.
NOTE: the measurements are taken on the basis of the set grid frequency: incorrect configuration
of the parameter may lead to abnormal measurements and protection
Ekip Touch is supplied with the parameter setting that suits the ordered configuration.